VFD Energy Savings Calculator

Estimate annual fan or pump energy savings when replacing damper, throttling valve or constant-speed control with variable-speed operation, based on affinity law principles.

Equipment Type
30%100%
Existing Control Method

Existing annual energy

239,805kWh

Existing annual cost

28,777EUR

VFD annual energy

121,960kWh

Annual energy savings

117,845kWh

Annual cost savings

14,141EUR

Relative savings

49.1%

Input power vs speed

0%25%50%75%100%30%50%70%90%100%Average speed / flow
Damper (existing) VFD (variable speed)

Estimates are based on simplified affinity-law part-load curves with an allowance for drive and motor losses, assuming operation at a single average speed. Actual savings depend on the load profile, static head, system curve and control strategy. Results are indicative and should not replace a detailed system energy analysis.

How the estimate works

Centrifugal fans and pumps follow the affinity laws: flow scales with speed, pressure with the square of speed and shaft power with the cube of speed. Mechanical throttling — dampers on fans, valves on pumps — reduces flow but leaves the motor running near rated speed, so much of the input power is wasted across the throttling element.

The calculator compares a simplified part-load power curve for the existing control method against cube-law variable-speed operation with an allowance for drive and motor losses. It assumes the system operates at a single average speed for all operating hours; real load profiles vary, and systems with significant static head deviate from the ideal cube law.